Cooling towers can be combined in several combinations to make the cooling more effective compared to the current space. Vestas aircoil cooling towers are open cooling towers and named OCT. The OCT01 and OCT02 indicates the size of the tower and the following describes the combination of cells. OCT01HB01-1 is a small tower with high bottom pan, one cell in one row.
Silencers
To comply with a specific noise requirement, the OCT cooling towers can easely be build up with silencers to reduce the noise level. Pre-fabricated moduls of silencers are simply to mount upon a existing tower.
|
|
|
OCT - |
No. of cells |
Length mm. |
Width mm. |
Heigh mm. |
Dry weight Kg. |
Operational weight Kg. |
Max flow m 3/h |
|
01HB01-1 |
1 |
1050 |
1140 |
3155 |
570 |
900 |
24,3 |
|
01HB02-1 |
2 |
2100 |
1140 |
3155 |
1140 |
1800 |
48,6 |
|
01HB03-1 |
3 |
3150 |
1140 |
3155 |
1710 |
2700 |
72,9 |
|
01HB02-2 |
4 |
2100 |
2100 |
3155 |
2280 |
3600 |
97,2 |
|
01HB03-3 |
6 |
3150 |
3150 |
3155 |
3420 |
5400 |
145,8 |
|
01HB04-4 |
8 |
4200 |
4200 |
3155 |
4560 |
7200 |
194,4 |
|
02HBL01-1 |
1 |
1350 |
1440 |
3250 |
790 |
1240 |
43,2 |
|
02HBL02-1 |
2 |
2700 |
1440 |
3250 |
1580 |
2480 |
86,4 |
|
02HBL03-1 |
3 |
4050 |
1440 |
3250 |
2370 |
3720 |
129,6 |
|
02HBL02-2 |
4 |
2700 |
2690 |
3250 |
3160 |
4960 |
172,8 |
|
02HBL03-3 |
6 |
4050 |
3940 |
3250 |
4740 |
7440 |
259,2 |
|
02HBL04-4 |
8 |
5400 |
5190 |
3250 |
6320 |
9920 |
345,6 |
|
HBH -model |
|
|
|
+ 500 mm |
+ 50 Kg |
+ 50 Kg |
|
|
|
|
|
|
|