Data sheet for OCT01-02 cooling towers

Cooling towers can be combined in several combinations to make the cooling more effective compared to the current space. Vestas aircoil cooling towers are open cooling towers and named OCT. The OCT01 and OCT02 indicates the size of the tower and the following describes the combination of cells. OCT01HB01-1 is a small tower with high bottom pan, one cell in one row.


Silencers

To comply with a specific noise requirement, the OCT cooling towers can easely be build up with silencers to reduce the noise level. Pre-fabricated moduls of silencers are simply to mount upon a existing tower.

OCT -

No.
of cells

Length
mm.

Width
mm.

Heigh
mm.

Dry weight
Kg.

Operational
weight Kg.

Max flow
m 3/h

01HB01-1

1

1050

1140

3155

570

900

24,3

01HB02-1

2

2100

1140

3155

1140

1800

48,6

01HB03-1

3

3150

1140

3155

1710

2700

72,9

01HB02-2

4

2100

2100

3155

2280

3600

97,2

01HB03-3

6

3150

3150

3155

3420

5400

145,8

01HB04-4

8

4200

4200

3155

4560

7200

194,4

02HBL01-1

1

1350

1440

3250

790

1240

43,2

02HBL02-1

2

2700

1440

3250

1580

2480

86,4

02HBL03-1

3

4050

1440

3250

2370

3720

129,6

02HBL02-2

4

2700

2690

3250

3160

4960

172,8

02HBL03-3

6

4050

3940

3250

4740

7440

259,2

02HBL04-4

8

5400

5190

3250

6320

9920

345,6

HBH -model

 

 

 

+ 500 mm

+ 50 Kg

+ 50 Kg